The Talentum® Flame Detector IR2 is designed to protect areas where open fires may be expected and detects almost all flames, including hydrocarbon fires with 4.3 μm emissions through to invisible fires such as hydrogen. This advanced detector is sensitive to flickering, low frequency infra-red radiation emitted by flames during combustion, even if the lens is contaminated by oil, dust, water, vapour, or ice.

Equipped with two IR sensors, the IR2 Flame Detector responds to different IR wavelengths to effectively discriminate between actual flames and spurious sources of radiation. It employs a combination of filters and signal processing techniques to avoid false alarms from flickering sunlight. The detector offers selectable output options of relay contacts or a 4-20 mA signal as standard, ensuring flexibility and reliability in various applications.

Features

  • Highest immunity to false sources
  • Tolerant of fumes, vapours, dust, and mist
  • Suitable for indoor areas
  • Detects flames through glass
  • Unaffected by convection currents, draughts, or wind
  • Proven response to multiple fuel types
  • Multi-spectrum detection
  • Selectable output options
  • Selectable response speed
  • Selectable sensitivity levels
  • Built-in auto and manual test
  • Low current consumption
  • Fast response to fire

Specifications

  • Housing Material : Die cast zinc alloy (ZA12)
  • Housing Colour : Blue RAL 240 50 35
  • Dimensions : 142(h) x 108(w) x 79(d) mm (5½”(h) x 4¼”(w) x 3⅛”(d))
  • Weight : 1.75 kg (3.8 lbs)
  • Cable Gland Entries : 2 x 20 mm (2 x ¾”)
  • Wiring : 1.0 to 4.0 mm² (12 – 18 AWG)
  • Supply Voltage : 14 to 30 Vdc
  • Response Time : Typically 4 seconds
  • Quiescent Current : 8 mA, RL2 energised; 4 mA, current loop, RL2 off; 3 mA, RL2 off
  • Alarm Current : 28 mA, RL1 & RL2 energised; 20 mA, current loop, RL1 & 2 off; 9 mA, RL1 energised
  • Power-up Time : 2 seconds max.
  • Test Signal Voltage : 14 to 30 Vdc
  • Relay Outputs : Programmable operation including latching or non-latching
  • Relay Maximum Ratings : Current 0.75 A, Voltage 48 Vdc, Power 30 W (resistive loads only)
  • Operating Temperature : -10°C to +55°C (+14°F to +131°F)
  • Storage Temperature : -20°C to +65°C (-4°F to +149°F)
  • Relative Humidity : 95% non-condensing
  • IP Rating : IP65
  • Range : High (Class 1)* 0.1 m² n-heptane at 25 m (82 ft); Low (Class 3) 0.1 m² n-heptane at 12 m (39 ft)
  • Field of View : 90° min. Cone
  • Operating Wavelength : IR 1.0 to 2.7 μm

Downloads